Skip to main content

Passer — Data Acquisition Controller

Passer is an industrial controller for high-frequency acquisition and primary signal processing from external sensors. It is important to understand: Passer is not a sensor, but an intelligent interface between physical sensors and the upper-level system.

Passer-V

Mental Model

"Not just 'capture the signal', but immediately answer: what's wrong with it?"

Passer digitizes the analog signal at up to 92 kHz and computes basic metrics: RMS, crest factor. The raw signal is transmitted to Larus, where spectral analysis (FFT) and detailed diagnostics are performed.

External sensor          Passer                    Larus
┌──────────────┐ ┌───────────────────┐ ┌────────────┐
│ ICP acceler- │──────► │ ADC (up to 92 kHz)│ │ │
│ ometer (V) │ 0–5V │ RMS │─────►│ Ethernet │
├──────────────┤ │ Crest factor │ │ → Larus │
│ Current │──────► │ Raw signal │ │ (FFT on │
│ transformer │ signal│ │ │ Larus) │
│ (T) │ │ │ │ │
└──────────────┘ └───────────────────┘ └────────────┘

Model Comparison

ParameterPasser-VPasser-T
Primary purposeVibration monitoringCurrent diagnostics of electric motors
Part numberPSRV-220PSRT-110
Signal typeAnalog, 0–5 VVoltage 0–400 V / current 0–5 A
Accuracy±0.3%±1.2%
Sensor installationSensor glued / screwed inCT snaps onto cable (15 min)
Shutdown requiredYes (sensor mounting)No
Hazardous areaRequires ATEX sensorsCT outside hazardous zone — safe
On-device processingRMS, crest factor (FFT — on Larus)MCSA (Motor Current Signature Analysis)
Operating temperature−40…+80 °C−25…+80 °C
InterfaceEthernet (2 × port)Ethernet (2 × port)
MountingDIN rail 35 mmDIN rail 35 mm

When to Choose Which?

Choose Passer-V if:

  • You need precise fault localization (bearing, gear mesh, imbalance)
  • You monitor mechanical equipment (pumps, compressors, gearboxes)
  • You need high-frequency analysis (up to 51.2 kHz)

Choose Passer-T if:

  • You need electric motor diagnostics without shutdown
  • Installation is in a hard-to-reach or hazardous area
  • Budget is limited (CTs only, no accelerometers)

Recommendation: Passer-T as a first step (fast, affordable, no shutdown), Passer-V — where precision matters (fault type, remaining life prediction). For a complete picture — use both on the same machine.

Passer-Sch

A separate variant — a mounting board for grounding monitoring in CVM100 enclosures. Not a data acquisition controller in the traditional sense.

More about Passer-Sch

Next